IRC requires 1 sq ft NFA per 150 sq ft attic floor (1/150 rule). With balanced system and vapor retarder, 1/300 may apply.
NFA (sq in) = Attic Area (sq ft) × 144 ÷ 150 (or ÷ 300 with vapor barrier)Balanced ventilation splits NFA equally between soffit intake and ridge or roof exhaust. Unbalanced systems reduce effectiveness.
Intake NFA = Exhaust NFA = Total NFA ÷ 2Divide required NFA by manufacturer-rated NFA per vent strip, panel, or continuous vent product.
Units = ceil(Required NFA ÷ NFA per Vent)Updated: July 2026
Need 1,440 sq in total NFA — 720 sq in soffit intake and 720 sq in ridge exhaust. Continuous ridge vent plus perforated soffit panels.
576 sq in total NFA at 1/150. Smaller attic still needs proportional vent area — do not skip ventilation on attached garages.
Measure existing soffit NFA from vent area. Match ridge vent NFA to at least 50% of total required, not less than existing intake.
Size soffit intake and ridge exhaust ventilation for code-compliant attic airflow. Enter attic floor area and vent product NFA (net free area) to get required vent counts and verify 50/50 intake-exhaust balance.